Request Pricing & Availability

NSN: 5925-00-001-7446
Part Number(s):
Quantity:
Company:
Name & Email:
Phone:
Order Terms | Privacy Policy    

NSN 5925-00-001-7446 Circuit Breaker

Manufacturer Part Numbers

Part Number Name Cage Code
ETN277500S22 Circuit Breaker 30086
5682D24G30 Circuit Breaker 89946

Management Codes

CTL: 9B----- (MOE: DN)
SOS: SMS
AAC: Not stocked, centrally procured # (non-stocked items). imm/service centrally managed but not stocked item. procurement will be initiated only after receipt of a requisition.
CIIC:
RC:
QUP: 1
UI: EA
SLC: 0

Freight Codes

NMF Desc: Circuit Breaker/switch Noi
NMFC: 061300
UFC: 34410
LTL: 77.5
LCL:
WCC: Electrical appliances, small
TCC: No special type of cargo code applicable
SHC: Other or no special handling required (sh)
ADC: Shipment is not a consolidation and does not exceed 84 inches in any dimension.
ACC: Instruments/equipment/supplies for radio, communications, electrical, laboratory, etc. (includes signal corps)
ASH: No special handling required.

Identification

DEMIL Code: A
DEMIL Integ:
ADPE: )
CRITL: X
ENAC:
ESD: )
HMIC: P
Schedule B: 8536200040 – Automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi
NIIN: 000017446

5925-00-001-7446 Datasheet

Actuator Function: Trip-reset
Actuator Position Designation: At pole two
Body Height: 3.875 inches nominal
Body Length: 6.500 inches nominal
Body Style: Multipole-single actuator type
Body Width: 4.125 inches nominal
Boss Height: 0.187 inches nominal
Case Material: Plastic
Center To Center Distance Between Terminals Parallel To Length: 3.937 inches nominal
Center To Center Distance Between Terminals Parallel To Width: 1.375 inches nominal
Circuit Protection Type: Overcurrent all locations
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width: 3.688 inches nominal
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length: 3.312 inches nominal
Frequency In Hertz: 400.0 all locations
Maximum Continuous Load Current Rating Per Pole: 100.0 amperes ac all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps: 10000.0 ac all locations
Mounting Facility Type And Quantity: 4 unthreaded hole
Operating Voltage Type And Rating Per Pole In Volts: 500.0 ac all locations
Storage Type: General purpose warehouse
Inclosure Protection Type For Which Designed: General purpose
Main Contact Tripping Mechanism Type: Trip free
Manual Actuator Type And Quantity: 1 toggle
Reset Method: Manual
Pole Quantity: 3
Terminal Type And Quantity: 6 tab, solder lug
Trip Delay Time In Seconds Per Rated Continuous Current: 300.000 minimum at 200 pct all locations and 900.000 maximum at 200 pct all locations and 60.000 minimum at 300 pct all locations and 120.000 maximum at 300 pct all locations
Trip Release Ambient Temp Rating: 50.0 deg celsius maximum all locations
Trip Release Characteristic: Time delay all locations
Trip Release Method: Thermal-magnetic all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent: 150.0 all locations
Unthreaded Mounting Hole Diameter: 0.190 inches nominal

Questions & Answers

What are the historical prices recorded for this stock number?
No pre-dated pricing for this NSN could be found.
What NATO entities are users of this NSN?
No recorded entities for this stock number.
How is national stock number 5925-00-001-7446 categorized?
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. may include provisions for manual operation. at least one set of contacts must be in series with the actuating element(s). a combination of semiconductor and passive devices may be used in lieu of contacts. for automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). for items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. excludes circuit breaker box and magneto "breaker" assemblies. see also switch (as modified); and controller.
Does this item require Demilitarization?
Non-usml/non-ccli - no demil or dod tsc required. department of commerce may impose licensing requirements to certain destinations. (note 9).
Is this item ITAR controlled?
No. This item is not ITAR Controlled.
When was this national stock number assigned to the federal catalog?
Sep 24, 1972