Request Pricing & Availability

NSN: 5925-00-004-7703
Part Number(s):
Quantity:
Company:
Name & Email:
Phone:
Order Terms | Privacy Policy    

Part Numbers

Item Number Item Description
TE111010WL Circuit Breaker
WC375/10-001 Circuit Breaker
W-C-375/10 Circuit Breaker

Master Requirement Codes

Code Translation
CPRW Denotes the action imparted by actuator operation.
CPRX An indication of the designated position of the actuator.
ADAU A measurement from the bottom to the top of the body, in distinction from depth.
ADAQ A measurement of the longest dimension of the body, in distinction from width.
AAQL The style designation indicating the configuration that most nearly corresponds to the appearance of the body.
ADAT A measurement taken at right angles to the length of the body, in distinction from thickness.
ADTV The element, compound, or mixture of which the case is fabricated, excluding any surface treatment.
CPRH Indicates the type of electrical condition that will cause the device to trip.
FREQ The cycles per second /hertz/ of the alternating current.
CPLM The maximum current load that each pole is rated to carry continuously.
CPRG Indicates the type and value of the maximum short circuit current that the item will successfully interrupt, per pole, at the specified rated voltage, expressed in amperes.
AXHR Indicates the type and number of facilities by which the item is mounted.
ABTD A measurement taken at right angles to the length of the mounting slot, in distinction from thickness.
CPRF Indicates the type and value of operating voltage for which each pole is designed to operate, expressed in volts.
AFJN The measure of sensitivity of the item to be packaged. a factor used by packaging engineers in devising proper cushioning in a package.
BBRJ The unusual or unique characteristic/s/ or quality/ies/ of an item which necessitates the establishment of a requirement for special handling.
BBRG Indicates the type of storage space required for an item in order to provide the degree of protection necessary to maintain serviceability standards.
CQXF Indicates the type of protection for which the inclosure is designed.
CPRR Indicates the type of mechanism provided for tripping main contacts.
CPRT Indicates the type and number of actuators provided for manual control.
CPRQ The means provided to reposition the mechanism so that the device is ready to function.
AKPX The number of poles included in the item.
ZZZK The document designator of the specification or standard which established the item of supply.
TTQY Indicates the type and number of terminals for providing electrical connection.
TEST The specification, standard, drawing, or similar instrument that specifies environmental and performance requirements or test conditions under which an item is tested and establishes acceptable limits within which the item must conform identified by an alphabetic and/or numeric reference number. includes the commercial and government entity (cage) code of the entity controlling the instrument.
CQWN The length of time, expressed in seconds, that an overload may exist before the device will trip at a specified continuous current.
CRCF The temperature of the medium surrounding the trip release at which it can be operated continuously.
CPRL Denotes the type of trip release action.
CPRJ The means by which the trip mechanism is released.
CPRN The continuous current rating per pole at which the device must trip in a specified time, expressed in percent.

TE111010WL Circuit Breaker

Cage 81348

Technical Definition

Circuit Breaker, also referenced with federal logistics item name code 00136 - A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. may include provisions for manual operation. at least one set of contacts must be in series with the actuating element(s). a combination of semiconductor and passive devices may be used in lieu of contacts. for automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). for items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. excludes circuit breaker box and magneto "breaker" assemblies. see also switch (as modified); and controller.

Technical Characteristics

Actuator Function (CPRW):
Trip-reset
Actuator Position Designation (CPRX):
At pole one
Body Height (ADAU):
3.380 inches nominal
Body Length (ADAQ):
6.310 inches nominal
Body Style (AAQL):
Single pole type
Body Width (ADAT):
1.370 inches minimum and 1.380 inches maximum
Boss Height (AJEC):
0.250 inches nominal
Case Material (ADTV):
Plastic
Circuit Protection Type (CPRH):
Overcurrent single location
Frequency In Hertz (FREQ):
60.0 single location
Maximum Continuous Load Current Rating Per Pole (CPLM):
10.0 amperes ac single location
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps (CPRG):
7500.0 ac single location
Mounting Facility Type And Quantity (AXHR):
4 slot
Mounting Slot Width (ABTD):
0.375 inches nominal
Operating Voltage Type And Rating Per Pole In Volts (CPRF):
120.0 ac single location
Fragility Factor (AFJN):
Moderately rugged
Special Handling Feature (BBRJ):
Magnetic
Storage Type (BBRG):
General purpose warehouse
Inclosure Protection Type For Which Designed (CQXF):
Corrosion resistant
Main Contact Tripping Mechanism Type (CPRR):
Trip free
Manual Actuator Type And Quantity (CPRT):
1 toggle
Reset Method (CPRQ):
Manual
Pole Quantity (AKPX):
1
Specification/standard Data (ZZZK):
81348-w-c-375/10 government specification
Terminal Type And Quantity (TTQY):
2 compression
Test Data Document (TEST):
81348-w-c-375 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "nominal", etc.).
Trip Delay Time In Seconds Per Rated Continuous Current (CQWN):
2.000 maximum at 200 pct single location
Trip Release Ambient Temp Rating (CRCF):
40.0 deg celsius nominal single location
Trip Release Characteristic (CPRL):
Instantaneous single location and time delay single location
Trip Release Method (CPRJ):
Thermal-magnetic single location
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent (CPRN):
135.0 single location

National Stock Number (NSN)

5925-00-004-7703