Request Pricing & Availability

NSN: 5925-00-001-5942
Part Number(s):
Quantity:
Company:
Name & Email:
Phone:
Order Terms | Privacy Policy    

NSN 5925-00-001-5942 Circuit Breaker

Manufacturer Part Numbers

Part Number Name Cage Code
BACC182L10A Circuit Breaker 81205
6752-304-10 Circuit Breaker 82647
D6760-17-10 Circuit Breaker 82647

Management Codes

CTL: ------- (MOE: DS)
SOS: SMS
AAC: Not stocked, centrally procured # (non-stocked items). imm/service centrally managed but not stocked item. procurement will be initiated only after receipt of a requisition.
CIIC:
RC:
QUP: 1
UI: EA
SLC: 0

Freight Codes

NMF Desc: Circuit Breaker/switch Noi
NMFC: 061300
UFC: 34410
LTL: 77.5
LCL:
WCC: Electrical appliances, small
TCC: No special type of cargo code applicable
SHC: Other or no special handling required (sh)
ADC: Shipment is not a consolidation and does not exceed 84 inches in any dimension.
ACC: Instruments/equipment/supplies for radio, communications, electrical, laboratory, etc. (includes signal corps)
ASH: No special handling required.

Identification

DEMIL Code: A
DEMIL Integ:
ADPE: )
CRITL: X
ENAC:
ESD: )
HMIC: P
Schedule B: 8536200040 – Automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi
NIIN: 000015942

Technical Characteristics

Actuator Function: Trip-reset
Actuator Position Designation: At pole two
Body Height: 2.125 inches maximum
Body Length: 2.200 inches maximum
Body Style: Multipole-single actuator type
Body Width: 2.250 inches maximum
Bushing Length: 0.220 inches minimum and 0.280 inches maximum
Case Material: Plastic
Center To Center Distance Between Terminals Parallel To Length: 1.471 inches minimum and 1.501 inches maximum
Center To Center Distance Between Terminals Parallel To Width: 0.735 inches minimum and 0.751 inches maximum
Circuit Protection Type: Overcurrent all locations
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length: 1.780 inches minimum and 1.840 inches maximum
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width: 0.735 inches minimum and 0.751 inches maximum
Frequency In Hertz: 400.0 all locations
Maximum Continuous Load Current Rating Per Pole: 10.0 amperes ac all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps: 1500.0 ac all locations
Mounting Facility Type And Quantity: 6 threaded hole
Nominal Thread Size: 0.138 inches
Operating Voltage Type And Rating Per Pole In Volts: 200.0 ac all locations
Fragility Factor: Moderately rugged
Precious Material: Silver
Storage Type: General purpose warehouse
Unpackaged Unit Weight: 0.500 pounds
Inclosure Protection Type For Which Designed: General purpose
Internal Trip Release Configuration: Series trip all locations
Main Contact Tripping Mechanism Type: Trip free
Manual Actuator Type And Quantity: 1 push-pull
Reset Method: Manual
Pole Quantity: 3
Precious Material And Location: Terminal surfaces silver
Terminal Type And Quantity: 6 screw
Test Data Document: 81205-bacc182l10a drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
Thread Quantity Per Inch: 32
Thread Series Designator: Unc
Trip Delay Time In Seconds Per Rated Continuous Current: 10.000 minimum at 200 pct all locations and 65.000 maximum at 200 pct all locations
Trip Release Ambient Temp Rating: 25.0 deg celsius nominal all locations
Trip Release Characteristic: Time delay all locations
Trip Release Method: Thermal all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent: 150.0 all locations

Questions & Answers

What are the historical prices recorded for this stock number?
No pre-dated pricing for this NSN could be found.
What NATO entities are users of this NSN?
No recorded entities for this stock number.
How is national stock number 5925-00-001-5942 categorized?
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. may include provisions for manual operation. at least one set of contacts must be in series with the actuating element(s). a combination of semiconductor and passive devices may be used in lieu of contacts. for automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). for items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. excludes circuit breaker box and magneto "breaker" assemblies. see also switch (as modified); and controller.
Does this item require Demilitarization?
Non-usml/non-ccli - no demil or dod tsc required. department of commerce may impose licensing requirements to certain destinations. (note 9).
Is this item ITAR controlled?
No. This item is not ITAR Controlled.
When was this national stock number assigned to the federal catalog?
Sep 29, 1972