1. Home /
  2. FSC NSN Catalog /
  3. Circuit Breakers /
  4. AM2-D3-A-100-2

NSN AM2-D3-A-100-2

Circuit Breaker

A nut, flat on top and bottom having 6 flat sides. For items which have internal tapered or straight (parallel) pipe threads, specific electrical conduit size designation, and which when installed, provide a method of tightening to lock the connection, see locknut, electrical conduit. See also locknut, tube fitting. For items having a thickness (or height) exceeding two times the width across the flats, use post, electrical-mechanical equipment. (when height or thickness and/or width across the flats is designated as a tolerance dimension, the maximum dimension will be used to determine compliance.)

at each pole actuator position designation, multipole-multiple actuator type body style, 2.480 inches minimum and 2.520 inches maximum body length, magnetic blowout arc quenching method, trip-reset actuator function.

NSN 5925-01-285-0397 Datasheet

(NSN) National Stock Number
5925-01-285-0397
(FSC) Federal Supply Classification
5925 - Circuit Breakers
(NIIN) National Item Identification Number
01-285-0397
Requires Demilitarization
Yes
(INC) Item Name Code
00136
Date
Sun, Sep 4, 1988
Schedule B Code
8536200040
Actuator Function
trip-reset
Actuator Position Designation
at each pole
Arc Quenching Method
magnetic blowout
Body Length
2.480 inches minimum and 2.520 inches maximum
Body Style
multipole-multiple actuator type
Body Width
1.480 inches minimum and 1.520 inches maximum
Boss Height
0.120 inches minimum and 0.160 inches maximum
Center To Center Distance Between Terminals Parallel To Length
1.918 inches minimum and 1.958 inches maximum
Center To Center Distance Between Terminals Parallel To Width
0.730 inches minimum and 0.770 inches maximum
Circuit Protection Type
overcurrent all locations
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.730 inches minimum and 0.770 inches maximum
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.042 inches minimum and 2.082 inches maximum
External Actuator Linkage Arrangement
one and two linked
Fragility Factor
moderately rugged
Frequency In Hertz
60.0 all locations
Inclosure Protection Type For Which Designed
fungus resistant and humidity resistant and moisture resistant and shock resistant and vibration resistant
Internal Trip Release Configuration
series trip all locations
Main Contact Tripping Mechanism Type
trip free
Manual Actuator Type And Quantity
2 toggle
Material
plastic case
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac and 100.0 amperes dc all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac and 5000.0 dc all locations
Mounting Facility Type And Quantity
4 threaded hole(s)
Mounting Surface To Terminal End Distance
2.441 inches minimum and 2.521 inches maximum
Nominal Thread Size
0.138 inches
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac and 65.0 dc all locations
Pole Quantity
2
Reset Method
manual
Storage Type
general purpose warehouse
Terminal Type And Quantity
4 threaded stud
Thread Quantity Per Inch
32
Thread Series Designator
unified national coarse (unc)
Trip Release Characteristic
time delay all locations
Trip Release Method
magnetic-hydraulic all locations
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct and 18.000 maximum at 200 pct all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
Unpackaged Unit Weight
6.500 ounces nominal

Identification

Demilitarization Code
A - Items subject to the export administration regulations (ear) in parts 730-774 of title 15, code of federal regulations (cfr) (ccli or ear99) and determined by dod to present a low risk when released out of dod control. No demil, mut, or end use certificate is required. May require an export licensefrom doc.
Precious Metals Indicator
A - Item does not contain precious metal.
Hazardous Metals Indicator
P - Indicates there is no information in the hmirs. The nsn is in a fsc in table ii of fed std 313 and a msds may be required by the user. The requirement for a msds is dependent on a hazard determination of the supplier or the intended end use of item.
Pseudo Item Name Code
0000136

Cross Reference

CAGE Codes

74193
Eaton Corp Heinemann Products Commercial Controls Div
U.s./canadian manufacturers

Freight Information

Air Commodity
HZ -
Air Dimension
A - Shipment is not a consolidation and does not exceed 84 inches in any dimension.
National Motor Freight Class Rating
W - Rating variable
Special Handling
9 - Other or no special handling required (sh)
Type of Cargo
Z - No special type of cargo code applicable
Uniform Freight Classification Item Number
35205
Water Commodity
72D - Communications/electronics, other than sigint/ew or comsec repair parts and components
National Motor Freight Classification Item Number
063160

Schedule B & Trade

Schedule B
8536-20-0040
Description
automatic circuit breakers, for a voltage not exceeding 1,000 v, nesoi
End Use
20005 - Electric apparatus
Unit of Quantity
NO
USDA
Yes
(SITC) Standard International Trade Classification
77252
(NAICS) North American Industrial Classification System
335313

Questions & Answers

  1. What is the FSCG of the NSN 5925-01-285-0397?

    The FSCG of the NSN 5925-01-285-0397 is 5925

  2. Does the NSN 5925-01-285-0397 have a Schedule B code assigned?

    Yes, the Schedule B code is 8536200040

  3. Does NSN 5925-01-285-0397 require demilitarization?

    Items subject to the export administration regulations (ear) in parts 730-774 of title 15, code of federal regulations (cfr) (ccli or ear99) and determined by dod to present a low risk when released out of dod control. No demil, mut, or end use certificate is required. May require an export licensefrom doc.

  4. Does NSN 5925-01-285-0397 contain precious materials?

    Item does not contain precious metal.

  5. Does NSN 5925-01-285-0397 contain hazardous materials?

    Indicates there is no information in the hmirs. The nsn is in a fsc in table ii of fed std 313 and a msds may be required by the user. The requirement for a msds is dependent on a hazard determination of the supplier or the intended end use of item.

  6. When the NSN 5925-01-285-0397 was assigned to the Federal Catalog?

    It was assigned 38 years ago, on Sun, Sep 4, 1988

Globe Transparent
Get in Touch
Looking for technical parts, product details, or custom project planning? Our team has you covered with end-to-end support every step of the way.
Contact Us

Pricing & Availability

Send us a request for quote using the form below. Our team will contact you with an up to date pricing and availability quote ASAP.

Recent Updates

Last Update: 1 day ago
View History