Secure Ordering: +1 (757) 528-8028
NationalStockNumber.info
NationalStockNumber.INFO

Worldwide distributor of NSN parts and consumables located in the USA.

Circuit Breaker

Model / MPN: SW261 | NSN: 5925-00-061-4346
ITAR Registered seal

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating elemen (s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified) ; and controller.

Product Details
NATO Stock Number
5925-00-061-4346
Sold in multiples of
EA
DEMIL
NO
Body Style
Multipole-multiple actuator type
Body Length
2.500 inches
Body Width
1.500 inches
Case Material
Plastic
Center To Center Distance Between Terminals Parallel To Length
1.935 inches
Center To Center Distance Between Terminals Parallel To Width
0.750 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches
Boss Height
0.125 inches
Mounting Surface To Terminal End Distance
2.359 inches
Pole Quantity
2
Mounting Facility Type And Quantity
4 threaded hole
Thready Qty Per Inch (tpi)
32
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations
Operating Voltage Type And Rating Per Pole In Volts
230.0 ac all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
Circuit Protection Type
Overcurrent all locations
Trip Release Method
Magnetic all locations
Trip Release Characteristic
Time delay all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
Ultimate Trip Time Per Pole In Seconds
1.010 all locations and 5.450 all locations
Ultimate Trip Time Per Pole In Seconds
1.010 and 5.450 all locations
Reset Method
Manual
Main Contact Tripping Mechanism Type
Trip free
Manual Actuator Type And Quantity
2 toggle
Actuator Function
Trip-reset
Actuator Position Designation
At each pole
External Actuator Linkage Arrangement
One and two linked
Internal Trip Release Configuration
Series trip w/auxiliary load terminal all locations
Thread Size
0.138 inches
Trip Delay Time In Seconds Per Rated Continuous Current
0.250 at 200 pct all locations and 0.800 at 200 pct all locations
Trip Delay Time In Seconds Per Rated Continuous Current
0.250 at 200 pct and 0.800 at 200 pct all locations
Frequency In Hertz
60.0 all locations
Thread Series Designator
Unc
Terminal Type And Quantity
6 threaded stud
SW261 Series Parts

Pricing and Availability

Send us a request for quote using the form below. Our team will contact you with an up to date pricing and availability quote ASAP.

Qty:
Email Address:
Phone Number:
Your name:
Company:
Privacy    Terms

Certified Quality Assurance  Quality check icon

  •   ISO 9001:2015 + AS9120B
  •   Counterfeit Parts Prevention
  •   100% Product Inspections
  •   7 Year Record Retention
  •   On Time Delivery
  •   HAZMAT Certified
  •   Worldwide Shipping
SW261 Cross Reference