Circuit Breaker

Model / MPN: 72020 | NSN: 5925-00-109-9161
ITAR Registered seal

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating elemen (s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified) ; and controller.

Product Details
NATO Stock Number
5925-00-109-9161
Sold in multiples of
1 EA
DEMIL
NO
Body Style
Multipole-single actuator type
Body Length
17.000 inches
Body Width
Between 8.000 inches and 8.500 inches
Unthreaded Mounting Hole Diameter
1.031 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
14.750 inches
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.750 inches
Pole Quantity
3
Mounting Facility Type And Quantity
4 unthreaded hole
Maximum Continuous Load Current Rating Per Pole
800.0 amperes ac all locations
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations
Trip Release Characteristic
Time delay all locations
Reset Method
Manual
Manual Actuator Type And Quantity
1 toggle
Trip Delay Time In Seconds Per Rated Continuous Current
280.000 at 200 pct all locations and 950.000 at 200 pct all locations
Trip Release Ambient Tempurature Rating
40.0 degrees celsius all locations
Frequency In Hertz
60.0 all locations
Special Test Features
Dielectric strength must pass equivalent of 1960v between live parts and ground and between poles for 1 second in both open and closed positions; must interrupt 350 percent at 60 hz of its rated current at 208v for 30 operations at 10 second intervals without undue burning of contacts

Pricing and Availability

Send us a request for quote using the form below. Our team will contact you with an up to date pricing and availability quote ASAP.

Qty:
Email Address:
Phone Number:
Your name:
Company:
Privacy    Terms

Certified Quality Assurance  Quality check icon

  •   ISO 9001:2015 + AS9120B
  •   Counterfeit Parts Prevention
  •   100% Product Inspections
  •   7 Year Record Retention
  •   On Time Delivery
  •   HAZMAT Certified
  •   Worldwide Shipping
72020 Cross Reference
  • 66C41162